The effect of insulating barriers on AC breakdown voltage in inhomogeneous field

  • A. Kara*
  • , E. Onal
  • , O. Kalenderli
  • , K. Mardikyan
  • *Bu çalışma için yazışmadan sorumlu yazar
  • Istanbul Technical University

Araştırma sonucu: Kitap/Rapor/Konferans Bildirisinde BölümKonferans katkısıbilirkişi

24 Atıf (Scopus)

Özet

In this study, the effect of insulating barriers on the breakdown voltage of air in inhomogeneous field is observed. Tests are conducted in order to measure the 50 Hz AC breakdown voltage of small air gaps (up to 50 mm) formed by hemispherically capped rod-plane electrodes with an insulating barrier between them. Energized rod and grounded plane gaps are studied with the flat insulating barriers that have three different diameters. The results of the test series show how the breakdown voltage varies with the distance between the electrodes, the size and the material of the barrier, the relative position of the electrodes and the barrier between them. As a result, all three materials show nearly same effect when they are used as a barrier, the breakdown voltage varies due to the size of the barriers and the maximum flashover voltages are observed when the barriers are positioned at the nearest point to the rod electrode and the small sized barriers become effective only in very small air gaps.

Orijinal dilİngilizce
Ana bilgisayar yayını başlığı2006 IEEE Mediterranean Electrotechnical Conference, MELECON 2006 - Circuits and Systems for Signal Processing, lnformation and Communication Technologies, and Power Sources and Systems
Sayfalar1206-1208
Sayfa sayısı3
Yayın durumuYayınlandı - 2006
Etkinlik2006 IEEE Mediterranean Electrotechnical Conference, MELECON 2006 - Benalmadena, Malaga, Spain
Süre: 16 May 200619 May 2006

Yayın serisi

AdıProceedings of the Mediterranean Electrotechnical Conference - MELECON
Hacim2006

???event.eventtypes.event.conference???

???event.eventtypes.event.conference???2006 IEEE Mediterranean Electrotechnical Conference, MELECON 2006
Ülke/BölgeSpain
ŞehirBenalmadena, Malaga
Periyot16/05/0619/05/06

Parmak izi

The effect of insulating barriers on AC breakdown voltage in inhomogeneous field' araştırma başlıklarına git. Birlikte benzersiz bir parmak izi oluştururlar.

Alıntı Yap