Özet
The paper analyzes laboratory ferroresonance measurements taken on an example of a three-phase three-legged power transformer. Ferroresonance occurrs due to a nonlinear inductance, capacitance and periodic voltage source in the network. A transformer becomes ferroresonant during an irregular circuit-breaker operation, when the interaction between the transformer nonlinear magnetizing inductances and phase-to-ground capacitances generate sustained distorted overvoltages. The measurement results and voltage waveforms show the presence of high and sustained ferroresonant overvoltages and a harmonic spectrum containing higher harmonics.
| Orijinal dil | İngilizce |
|---|---|
| Sayfa (başlangıç-bitiş) | 195-199 |
| Sayfa sayısı | 5 |
| Dergi | Elektrotehniski Vestnik/Electrotechnical Review |
| Hacim | 84 |
| Basın numarası | 4 |
| Yayın durumu | Yayınlandı - 2017 |
Parmak izi
Laboratory ferroresonance measurements in power transformers' araştırma başlıklarına git. Birlikte benzersiz bir parmak izi oluştururlar.Alıntı Yap