Indoor and outdoor pullout tests for retrofit anchors in low strength concrete

  • Derya Cavunt
  • , Yavuz S. Cavunt*
  • , Alper Ilki
  • *Bu çalışma için yazışmadan sorumlu yazar
  • Istanbul Technical University

Araştırma çıktısı: Dergi yayınıMakaleHakem

Özet

In this study, pullout capacities of post-installed deformed bars anchored in low strength concrete using different bonding materials are investigated experimentally. The experimental study was conducted under outdoor and indoor conditions; on the beams of an actual reinforced concrete building and on concrete bases constructed at Istanbul Technical University (ITU). Ready-mixed cement based anchorage mortar with modified polymers (M1), ordinary cement with modified polymer admixture (M2), and epoxy based anchorage mortar with two components (E) were used as bonding material. Furthermore, test results are compared with the predictions of current analytical models. Findings of the study showed that properly designed cement based mortars can be efficiently used for anchoring deformed bars in low quality concrete. It is important to note that the cost of cement based mortar is much lower with respect to conventional epoxy based anchorage materials.

Orijinal dilİngilizce
Sayfa (başlangıç-bitiş)951-968
Sayfa sayısı18
DergiComputers and Concrete
Hacim18
Basın numarası5
DOI'lar
Yayın durumuYayınlandı - 1 Kas 2016