Özet
This paper presents a detailed analysis of the doubly fed induction generator (DFIG) and converters by taking into account magnetic saturation of both DFIG and step-up transformer under symmetrical and asymmetrical faults. 2.5 MW DFIG is modeled through Finite Element Analysis software package and coupled with circuit and dynamic system simulators for accurate electromagnetic, drive and controller simulations. The effects of different type of utility grid faults on the DFIG rotor fluxes are analyzed and the FFT analysis of the rotor fluxes is carried to correlate the harmonic content of the rotor fluxes with the fault types. The study would provide guidance in developing advanced control and protection techniques for the DFIG system during fault conditions. The simulation results are verified with the 7.5 Hp experimental DFIG system.
| Orijinal dil | İngilizce |
|---|---|
| Ana bilgisayar yayını başlığı | 2013 IEEE Energy Conversion Congress and Exposition, ECCE 2013 |
| Sayfalar | 2270-2276 |
| Sayfa sayısı | 7 |
| DOI'lar | |
| Yayın durumu | Yayınlandı - 2013 |
| Harici olarak yayınlandı | Evet |
| Etkinlik | 5th Annual IEEE Energy Conversion Congress and Exhibition, ECCE 2013 - Denver, CO, United States Süre: 15 Eyl 2013 → 19 Eyl 2013 |
Yayın serisi
| Adı | 2013 IEEE Energy Conversion Congress and Exposition, ECCE 2013 |
|---|
???event.eventtypes.event.conference???
| ???event.eventtypes.event.conference??? | 5th Annual IEEE Energy Conversion Congress and Exhibition, ECCE 2013 |
|---|---|
| Ülke/Bölge | United States |
| Şehir | Denver, CO |
| Periyot | 15/09/13 → 19/09/13 |
BM SKH
Bu sonuç, aşağıdaki Sürdürülebilir Kalkınma Hedefine/Hedeflerine katkıda bulunur
-
SKH 7 Erişilebilir ve Temiz Enerji
Parmak izi
Harmonic analysis of doubly fed induction generator based utility interactive wind turbine systems during fault conditions' araştırma başlıklarına git. Birlikte benzersiz bir parmak izi oluştururlar.Alıntı Yap