Energy assessment of CRAH bypass for enclosed aisle data centers

  • Syracuse University

Araştırma çıktısı: Kitap/Rapor/Konferans Bildirisinde BölümKonferans katkısıHakem

9 Atıf (Scopus)

Özet

Temperature non-uniformities in traditional data centers can be eliminated or at least reduced by utilizing containment systems. As all servers receive the same inlet air temperature in a contained configuration, the cooling system can be operated more efficiently at a higher temperature, which also increases the potential for free cooling through various economizer modes. However, enclosed aisle configurations require computer room air handler (CRAH) fans to operate at a higher speed and provide entire rack air flow through the perforated tiles, unlike open aisle data centers that can make up a fraction of server air from the data center air space. Hence, the traditional enclosed aisle configuration is likely to consume more fan power. This study confirms that enclosing the aisle does not guarantee optimum cooling infrastructure power in air cooled data centers. Proposed CRAH bypass configuration for enclosed aisle data centers provides a fraction of the tile airflow rate through a set of bypass fans while CRAH fans operate at lower speeds. These low-lift fans operate across a pressure difference between the room and plenum, which is significantly less than the flow resistance of CRAH units. Meanwhile, CRAH fans operate at lower speeds and consume less energy. Accordingly, a certain bypass air fraction with respect to total rack air flow rate leads to a minimum cooling infrastructure power for a particular configuration. This study investigates energy savings potential of the enclosed aisle data centers with CRAH bypass configuration utilizing a calibrated flow network model for estimating the energy consumption of air movers as well as a thermodynamic modeling tool to evaluate the off-design performance of major components of data center cooling infrastructure. Hour-by-hour annual energy simulations complement the energy assessment for 7 U.S. cities considering indirect air side economizer operation.

Orijinal dilİngilizce
Ana bilgisayar yayını başlığıProceedings of the 15th InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITherm 2016
YayınlayanInstitute of Electrical and Electronics Engineers Inc.
Sayfalar433-439
Sayfa sayısı7
ISBN (Elektronik)9781467381215
DOI'lar
Yayın durumuYayınlandı - 20 Tem 2016
Etkinlik15th InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITherm 2016 - Las Vegas, United States
Süre: 31 May 20163 Haz 2016

Yayın serisi

AdıProceedings of the 15th InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITherm 2016

???event.eventtypes.event.conference???

???event.eventtypes.event.conference???15th InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITherm 2016
Ülke/BölgeUnited States
ŞehirLas Vegas
Periyot31/05/163/06/16

Bibliyografik not

Publisher Copyright:
© 2016 IEEE.

Finansman

This research is supported by The New York State Energy Research and Development Authority (NYSERDA) through Award Number 41202. We acknowledge additional support by Tate Access Floors, Inc. through lending CRAH bypass fans for the duration of this research.

FinansörlerFinansör numarası
New York State Energy Research and Development Authority41202

    BM SKH

    Bu sonuç, aşağıdaki Sürdürülebilir Kalkınma Hedefine/Hedeflerine katkıda bulunur

    1. SKH 7 - Erişilebilir ve Temiz Enerji
      SKH 7 Erişilebilir ve Temiz Enerji
    2. SKH 11 - Sürdürülebilir Şehirler ve Topluluklar
      SKH 11 Sürdürülebilir Şehirler ve Topluluklar

    Parmak izi

    Energy assessment of CRAH bypass for enclosed aisle data centers' araştırma başlıklarına git. Birlikte benzersiz bir parmak izi oluştururlar.

    Alıntı Yap