Özet
In a circuit where the load is nonlinear or the source has forms the apparent power is defined as [Formula Ommitted] are reviewed. It is well known that the distortion power D is generated by the cross products of voltage and current harmonics of different frequencies. Accurate experiments are performed to measure the distortion power for a great variety of nonlinear load conditions of a 25 kVA transformer for a range of total harmonic current (THDv) and total harmonic voltage (THDv) distortions. The computed distortion power D as a function of voltage and current harmonics of unlike frequencies is validated by measurements: one concludes that a proper interpretation of Budeanu's definition is correct and agrees with measured results.
| Orijinal dil | İngilizce |
|---|---|
| Sayfa (başlangıç-bitiş) | 50-52 |
| Sayfa sayısı | 3 |
| Dergi | IEEE Power Engineering Review |
| Hacim | 19 |
| Basın numarası | 5 |
| DOI'lar | |
| Yayın durumu | Yayınlandı - May 1999 |
| Harici olarak yayınlandı | Evet |