Breakdown characteristics of CO2 containing 0.125% of SF6

Emel Onal*, Ozcan Kalenderli, Kevork Mardikyan

*Bu çalışma için yazışmadan sorumlu yazar

Araştırma sonucu: ???type-name???Konferans katkısıbilirkişi

Özet

AC breakdown strengths of CO2, SF6 and a mixture of CO2+SF6 containing 0.125% of SF6 in nonuniform field were experimentally studied. The electrode gap spacing and the relative gas pressure were varied within the range of 5-25 mm and of 100-500 kPa respectively. The experimental results have shown that the addition of SF6 to CO2 causes a significant increase the AC breakdown voltage with respect to CO2. Even at about pressures of 300 kPa and 25 mm gap spacing breakdown voltage of mixture were obtained 15% higher than that of pure SF6 and 54% higher than that of pure CO2.

Orijinal dilİngilizce
Ana bilgisayar yayını başlığıIEE Conference Publication
YayınlayanIEE
Sayfalar3.301.P3-3.304.P3
Baskı467
ISBN (Basılı)0852967195
Yayın durumuYayınlandı - 1999
EtkinlikProceedings of the 1999 11th International Symposium on 'High Voltage Engineering' (ish99) - London, UK
Süre: 23 Ağu 199927 Ağu 1999