Theoretical and experimental examination of air conditioner heat exchangers

Zafer Gemici, Nilufer Egrican, Aliihsan Koca*

*Corresponding author for this work

Research output: Contribution to journalArticlepeer-review

2 Citations (Scopus)

Abstract

Heat and mass transfer characteristics of finned-tube heat exchangers under dehumidifying and dry conditions are examined both theoretically and experimentally in the present study. Six types of heat exchangers were tested on an experimental facility. It was determined that there is less than 1 °C of outlet air temperature difference between computer program results and literature for water and R22 as a refrigerant. The outlet air specific humidity difference between them is less than 6.44% for water and 9% for R22. According to the experimental results, louvers on fin cause an increase of airside heat transfer coefficient of about 50% or 100%.

Original languageEnglish
Pages (from-to)681-686
Number of pages6
JournalInternational Communications in Heat and Mass Transfer
Volume37
Issue number6
DOIs
Publication statusPublished - Jul 2010
Externally publishedYes

Keywords

  • Finned tube
  • Heat exchanger
  • Heat transfer

Fingerprint

Dive into the research topics of 'Theoretical and experimental examination of air conditioner heat exchangers'. Together they form a unique fingerprint.

Cite this