Abstract
This paper deals with a new method of evaluating lightning impulse voltage parameters. For this purpose, three different types of impulse signals were used for analysis. The main point of the study focuses on the k-factor and wavelet transform methods to attenuate oscillations and overshoots that occur in impulse voltages. In this manner, as an alternative method to the k-factor approach, which is proposed in the IEC Standard 60060-1, the wavelet-based filtering approach is presented and its last approximation sub-band is described as de-noised data. Under the comparisons of the calculated signal parameters, the wavelet application was found to be a powerful method as much as the k-factor filtering in terms of a mathematical solution to the related problem.
| Original language | English |
|---|---|
| Pages (from-to) | 2843-2852 |
| Number of pages | 10 |
| Journal | Arabian Journal for Science and Engineering |
| Volume | 43 |
| Issue number | 6 |
| DOIs | |
| Publication status | Published - 1 Jun 2018 |
Bibliographical note
Publisher Copyright:© 2017, King Fahd University of Petroleum & Minerals.
Keywords
- High-voltage impulse signals
- IEC 60060-1
- k-factor filtering
- Multi-resolution wavelet analysis
Fingerprint
Dive into the research topics of 'The Wavelet-Based Filtering Method as an Alternative to k-Factor Filtering for High-Voltage Impulse Signals'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver