Design and implementation of an identifier system for inter-area power oscillations

Tevhid Atalik*, Mustafa Dogan, Turan Demirci

*Corresponding author for this work

Research output: Contribution to journalArticlepeer-review

5 Citations (Scopus)

Abstract

Identifying inter-area oscillations can be a challenge for interconnected grids. Two identifier algorithms (FBMSWA and TBR-EMD) proposed to detect these oscillations are comparatively tested in this research. FBMSWA is implemented with T-STATCOM to damp out 0.15 Hz low-frequency inter-area oscillation after interconnection Turkey with ENTSO-E. Developed TBR-EMD algorithm has certain achievements, e.g. admissible for real time, handling intermittency problem of EMD, proved by real data.

Original languageEnglish
Pages (from-to)86-95
Number of pages10
JournalElectric Power Systems Research
Volume122
DOIs
Publication statusPublished - May 2015
Externally publishedYes

Bibliographical note

Publisher Copyright:
©2015 Elsevier B.V. All rights reserved.

Keywords

  • Empirical mode decomposition (EMD)
  • FFT
  • Hilbert-Huang transform (HHT)
  • Inter-area oscillations
  • STATCOM
  • Target-based refinement

Fingerprint

Dive into the research topics of 'Design and implementation of an identifier system for inter-area power oscillations'. Together they form a unique fingerprint.

Cite this