Abstract
Extracting negative phase sequence components from the three-phase ac voltages and currents has been a long standing challenge for protection engineers. This paper presents a novel numeric, three-phase filtering algorithm for extracting the negative phase sequence components from sampled three phase measurements. The algorithm has been formulated to be suitable for use in a numeric relay to determine either the absolute value of the negative phase quantities or the relative value of the negative phase sequence to the positive phase sequence measured at the operating point. To demonstrate the capabilities of the algorithm, the paper presents results that show that the level of negative phase sequence components can typically be extracted within 30 milliseconds following a disturbance using a basic post-extraction smoothing filter. This demonstration used a nominal sampling rate of 1200 samples per second and an automatic frequency tracking algorithm to maintain synchronisation between the sampling clock and the power system frequency.
Original language | English |
---|---|
Pages | 1073-1077 |
Number of pages | 5 |
Publication status | Published - 2002 |
Event | 2002 IEEE Power Engineering Society Summer Meeting - Chicago, IL, United States Duration: 21 Jul 2002 → 25 Jul 2002 |
Conference
Conference | 2002 IEEE Power Engineering Society Summer Meeting |
---|---|
Country/Territory | United States |
City | Chicago, IL |
Period | 21/07/02 → 25/07/02 |
Keywords
- Negative Phase Sequence Signals
- Protection Relaying and Numeric Relaying